FlowGuardian®

Water leak detection, high water usage alarm system and BREEAM WAT 02 and WAT 03 credits

FlowGuardian®

A major water leak detection and sustainability solution

FlowGuardian® uses two flow meters — one situated at the site boundary and the other in a building — and actively monitors the mains water supply.

Benefits at a glance

Major mains water leak alarm

Excessive water usage alarm

Protects against damaging and costly water leaks

Monitors water usage

Saves on water bills

Can earn BREEAM WAT 02 and WAT 03 credits

Identifies leaks and excessive water usage

The system uses the flow rates and volumes from the internal flow meter to identify major water leaks and excessive water usage, as well as providing general water usage monitoring.

The programmable, discreet, wall-mounted control panel has a simple, interactive push-button LCD display with an audible buzzer alarm. All alarms are displayed continuously until corrected and reset on the system.

The wall-mounted panel is equipped with advanced communications and Modbus connectivity for onward communications to BMS and remote users, plus an option to control water isolation valves in the event of a water leak.

BREEAM WAT 02 and WAT 03 credits

FlowGuardian® provides flow monitoring and water leak detection in line with the defined BREEAM standards WAT 02 and WAT 03, and can earn BREEAM credits subject to a successful audit by an authorised assessor.

No handoff, no gaps, one number to call.

The detail.

Product code: FG.

Standards: BREEAM WAT 02, BREEAM WAT 03.

Power
  • Mains supply 110–230 VAC, 50/60Hz, 10W
Construction
  • IP66, ABS enclosure
Dimensions
  • H 250mm × W 175mm × D 75mm
Fixing
  • Control panel Surface mounted on internal wall
  • Flow meters Compression/flange fitting dependent on size of flow meter
Monitoring
  • Major underground water leak – difference between the internal and external flow meters.
  • Excessive volume within user specified daily time period
  • Excessive flow rate within user specified daily time period.
  • User-adjustable daily volume, flow rate and time period for continuous monitoring.
  • Flow meter fault monitoring.
  • Daily volume in litres and all time volume in cubic metres display.
  • Alarm data event log on FIFO basis.
Status and Alarm Indicators
  • 4 × 12 backlit LCD display
  • Audible buzzer alarm.
  • All alarms displayed continuously until corrected and reset on the system
Outputs
  • Mains Fail SPCO Relay (5A @ 250Vac)
  • Flow Alarm SPCO (5A @ 250Vac)
  • Flow Meter Fault SPCO (5A @ 250Vac)
  • Complete Power Failure SPCO (5A @ 250Vac)
  • Modbus RTU
  • All relays are clean volt-free contacts.
Two flow meters — one at the property boundary, one inside the building — monitor the mains supply; the difference between them identifies underground leaks.
Two flow meters — one at the property boundary, one inside the building — monitor the mains supply; the difference between them identifies underground leaks.

Explore the range.

The Andel team

Talk to Andel engineers about water sustainability.

Specifying at design stage? Learn how to specify water sustainability correctly with an accredited CPD session, delivered by Andel engineers.